Adjudication Order Parcel
Adjudication Order #A/O2017-006 for 4100 International Gateway
The above A/O was heard before the Ohio Board of Bldg Appeals on 8/1/2017 w/ the following results:
A variance against the A/O is given.
The A/O states OBC 503.1 ¿ the bldg height & area shall not exceed the limits specified in Table 503 based on the type of construction as determined by Section 602 & the occupancies as determined by Section 602 & the occupancies as determined by Section 302 except as modified hereafter. Each portion of a bldg separated by one or more fire walls complying w/ Section 706 shall be considered to be a separate bldg.
OBC1014.3 ¿ In occupancies other than Groups H-1, H-2, & H-3, the common path of egress travel shall not exceed 75 ft. In Group H-1, H-2 & H-3 occupancies, the common path of egress travel shall not exceed 25 ft.
OBC ¿ 1016.1 ¿ Exits shall be so located on each story such that the maximum length of exit access travel, measured from the most remote point w/in a story along the natural & unobstructed path of egress travel to an exterior door at the level of exit discharge, an entrance to a vertical exit enclosure, & exit passageway, a horizontal exit, an interior exit stairway or an exterior exit ramp, shall not exceed the distances given in Table 1016.1.
NFPA 30A, Sec. 7.3.6.5 ¿ The fuel dispensing area shall be located at street level, w/no dispenser located more than 50 ft from the vehicle exit to or entrance from, the outside of the bldg.
NFPA 30A, Sec. 7.3.6.6 ¿ The fuel dispensing area shall be limited to that required to serve not more than four vehicles at one time.
Variance is conditioned upon the following:
1. An additional stairway shall be installed in the other stairs located to the satisfaction of the bldg & fire officials.
2. This variance is granted based on the use, construction, occupant load, sq footage & level of activity identified on the approved construction documents including the maintenance of all bldg systems & any conditions required herein.
Variance is granted noting no objection of the Bldg & Fire Official.
The Board declares that any conditions required as part of the variance are inseparable & must be complied w/ in full; variance is dependent upon compliance w/ all conditions herein stated & lack of compliance w/ any portion of these conditions shall negate the entire variance. In addition, any conditions to the variance shall be incorporated into final permit drawings for examination & any appropriate fees shall be paid.
Dbaxter-daniel